Products

LSHF FIRE RESISTANT CABLE

Voltage Rating
300/500V, 450/750V or 600/1000V

Colour of identification
Insulation 1-Core Natural. (Orange for non-sheathed)

2-Core Brown and Blue

3-Core Brown, Black, Grey

4-Core Brown, Black, Grey and Blue
Over Sheath
Orange



Constructions
1. Conductors Plain annealed stranded copper conductor
2. Fire barrier Mica tape
3. Insulation Cross-Linked PE or LSHF compound
4. Filler (where applicable) LSHF or Polypropylene yarn
5. Binder Tape (where applicable) Polyester (mylar) tape / non-woven polyster tape
6. Bedding (for armoured cable) LSHF compound, type LTS 1 or ST8
7. Armouring (for armoured cable) Aluminium wires or Galvanized steel wires
8. Oversheath LSHF compound, type LTS 1, LTS 4 or ST8

XLPE INSULATED PVC OR LSHF SHEATHED POWER CABLE


Voltage Rating
600/1000V, 1800/3000V or 1900/3300V

Colour of identification
Insulation 1-Core Natural.

2-Core Brown and Blue

3-Core Brown, Black and Grey

4-Core Brown, Black, Grey and Blue
Over Sheath Black



Constructions
1. Conductors Plain annealed stranded copper conductor
2. Insulation Cross-Linked PE compound
3. Filler (where applicable) PVC or Polypropylene yarn
4. Binder Tape (where applicable) Polyester (mylar) tape/ non-woven polyester tape
5. Bedding (for armoured cable) Flame retardant PVC compound, type ST2, LSHF or ST8 compound
6. Armouring (for armoured cable) Aluminium wires or Galvanized steel wires
7. Oversheath Flame retardant PVC compound, type ST2, LSHF or ST8 compound

PVC INSULATED POWER CABLE
(Armoured)

Voltage Rating
600/1000V or 1900/3300V

Colour of identification
Insulation 1-Core Brown or Blue

2-Core Brown and Blue

3-Core Brown, Black and Grey

4-Core Brown, Black, Grey and Blue

5-Core & above White Core with Black Numbers
Over Sheath Black



Constructions
1. Conductors Plain annealed stranded copper conductor
2. Insulation Flame retardant PVC compound
3. Filler (where applicable) PVC or Polypropylene yarn
4. Binder Tape (where applicable) Polyester (mylar) tape/ non-woven polyester tape
5. Bedding (for armoured cable) Flame retardant PVC compund
6. Armouring (for armoured cable) Aluminium wires or Galvanized steel wires
7. Oversheath Flame retardant PVC compound

PVC INSULATED POWER CABLE
(Non-Armoured)

Voltage Rating
300/500V, 450/750V or 600/1000V

Colour of identification
Insulation 1-Core Brown, Blue,Green/Yellow, Red, Black or other colours as per customer's request.

2-Core Brown and Blue

3-Core Brown, Black and Grey

4-Core Brown, Black, Grey and Blue
Over Sheath Black, Grey, White



Constructions
1. Conductors Plain annealed stranded copper conductor
2. Insulation Flame retardant PVC compound
3. Filler (where applicable) PVC or Polypropylene yarn
4. Binder Tape (where applicable) Polyester (mylar) tape / non-woven polyster tape
5. Oversheath Flame retardant PVC compound

INSTRUMENTATION CABLE

Application:
Instrumentation Cables are designed for use in the provision of voice and data services and the interconnection of electrical equipment and instruments especially in and around process plants

Standard:
BS 5308 PART 2



Constructions
1. Conductors Plain annealed copper wires to BS 6360
2. Insulation PVC
3. Pairs Insulated cores are twisted to form a pair, and the length of lay of any pair shall not exceed 100mm
4. Colour Code Black/White with pair number printed on white core
5. Individual Screen (IS) (Optional) Aluminium / Polyester tape, with tinned copper drain wire 0.5mm²
6. Cabling The required number of pairs shall be assembled in concentric layers
7. Wrapping Polyester Binder tape
8. Collective Screen (OS) Aluminium / Polyester tape, with tinned copper drain wire 0.5mm²
9. Nylon Yarn For easy stripping
10. Bedding (optional) PVC
11. Armouring (optional) Galvanized steel wires to BS 1442
12. Outer sheath PVC

FLEXIBLE CABLE

250 / 440V PVC INSULATED, PVC SHEATHED
FLEXIBLE CABLE (BS 2004)

Colour of identification
Insulation 2-Core Blue and Brown

3-Core Blue, Brown,and Green / Yellow

4-Core Blue, Brown, Black and Green / Yellow
Over Sheath Grey or Custom made colour



Constructions
1. Conductors Flexible Copper Conductor
2. Insulation Polyvinyl Chloride (PVC) compound
3. Colour Black, Blue, Brown and Green with Single Yellow Line
4. Sheath Polyvinyl Chloride (PVC) compound
5. Colour According to customer request
6. Reference Standard BS2004
7. Printing SIGMA WIRE 250/440V (SIZE) X NO. OF CORE

LAN CABLE

Application:
Instrumentation Cables are designed for use in the provision of voice and data services and the interconnection of electrical equipment and instruments especially in and around process plants

Standard:
BS 5308 PART 2



Constructions
1. Conductors Plain annealed copper wires to BS 6360
2. Insulation PVC
3. Pairs Insulated cores are twisted to form a pair, and the length of lay of any pair shall not exceed 100mm
4. Colour Code Black/White with pair number printed on white core
5. Individual Screen (IS) (Optional) Aluminium / Polyester tape, with tinned copper drain wire 0.5mm²
6. Cabling The required number of pairs shall be assembled in concentric layers
7. Wrapping Polyester Binder tape
8. Collective Screen (OS) Aluminium / Polyester tape, with tinned copper drain wire 0.5mm²
9. Nylon Yarn For easy stripping
10. Bedding (optional) PVC
11. Armouring (optional) Galvanized steel wires to BS 1442
12. Outer sheath PVC